配电网模值差动保护的实现方法

Implementation method of phasor magnitude differential protection in distribution network

  • 摘要: 目前,基于光纤通道的电流差动保护主要是在配电网重点线路中使用,距离保护和过电流保护难以适应分布式新能源在配电网中占比快速增加的情况。5G 通信为电流差动保护提供了新的通道方式,但 5G 通信数据收发延时不一致,假同步会影响传统差动保护的性能。为此,基于 5G 通信,通过将两侧电流模值比值与保护总的动作系数比较、两侧电流模值之和与差动动作电流定值比较,再结合线路两侧故障方向判别等方法,实现线路区内外故障的识别。该方法经仿真试验,满足配电网对电流差动保护的性能要求。

     

    Abstract: At present, current differential protection based on fiber optic channels is mainly used in key power lines, and distance protection and overcurrent protection are difficult to meet the rapidly increasing proportion of distributed new energy in distribution networks. 5G communication provides a new channel for current differential protection, but the data transmission and reception delay of 5G communication is inconsistent, and false synchronization will affect the performance of traditional differential protection. Therefore, based on 5G communication, methods such as comparing the ratio of current modulus values on both sides with the total action coefficient of protection, comparing the sum of current modulus values on both sides with the differential action current setting, and combining fault direction discrimination on both sides of the line are proposed to achieve the identification of faults inside and outside the line area. This method has been simulated and tested to meet the performance requirements of current differential protection in distribution networks.

     

/

返回文章
返回