某特殊输电通道±800kV铁塔抗冰能力改造研究

Research on the ice protection capabilities of a ±800kV special channel of power transmission line

  • 摘要: 某±800kV 特高压输电线路属于特殊输电通道,且该输电线路实际覆冰厚度超过原设计标准。为保证该特殊输电通道的安全及电网的稳定运行,需对该输电线路进行防冰风险能力校验。经校验,除事故工况和不均匀覆冰工况导致杆塔主材或斜材承载力超限以外,其余工况均满足原设计条件且具备一定的防冰能力。同时,由于脱冰张力远超过原设计值,不均匀覆冰工况导致塔身部分交叉斜材及横担斜材杆件利用率超标。通过局部更换塔身及横担中不满足承载力要求的杆件,铁塔能够满足实际覆冰的承载力要求,并具备防冰抗风险能力。

     

    Abstract: A ±800kV UHV transmission line belongs to a special transmission channel. The actual icing thickness of the transmission line exceeds the original design standard. To ensure the safety of the special power transmission channel and the stable operation of the power grid, it is necessary to conduct an anti-icing risk capability verification for the transmission line. After verification, except for the accident condition and uneven icing condition that cause the bearing capacity of some main materials and diagonal members of the iron tower to exceed their limits, all the other conditions meet the original design requirements and possess a certain degree of anti-icing capability. Additionally, due to the ice-shedding tension far exceeding the original design value, the uneven icing condition cause the utilization of some cross diagonal members and cross arm diagonal members of the transmission tower body. By partially replacing the transmission tower body and cross arms members that can't meet the bearing capacity requirements, the transmission iron tower can meet the actual icing bearing capacity requirements and anti-icing risk.

     

/