发电机定子绕组主绝缘老化过程中局部放电特征与残余击穿电压关联分析

Correlation analysis between partial discharge characteristics and residual breakdown voltage during aging of main insulation of generator stator winding

  • 摘要: 对额定电压10.5 kV发电机定子绕组少胶环氧云母带主绝缘开展热-电联合加速老化试验,分析老化过程中 的局部放电特征参量变化与剩余击穿电压U 的关系。加速老化温度为155 ℃,加速老化电压为15.75 kV,每隔 b 500 h取样做局部放电测试并测量U 值,选取最大放电量、平均放电量、放电频率、斜度和峰度5个特征参量进 b 行研究。经计算可知,这5个特征参量与U 的Pearson相关系数绝对值都在0.98以上,放电频率的相关系数绝 b 对值最大(r=-0.996 9),其次是斜度(r=-0.997 6)。根据多元线性回归拟合得到的U 预测模型可知,R2=0.999 8, b RMSE=0.151 5 kV。结果表明,该特征参量组合能够准确反映主绝缘老化程度,可为发电机绝缘在线监测及剩余寿 命预测提供理论依据与数据参考。

     

    Abstract: The thermal electrical accelerated aging test was carried out on the main insulation of the low-resin epoxy mica tape of the stator winding of the generator with a rated voltage of 10.5 kV, and the change of partial discharge characteristic parameters during aging and the relationship with the residual breakdown voltage U were analyzed. The accelerated aging b temperature was 155 ℃ and the accelerated aging voltage was 15.75 kV. Partial discharge test was conducted every 500 and the U value was measured. Five characteristic parameters, maximum discharge capacity, average discharge capacity, b discharge frequency, slope, kurtosis, were selected for research. The calculation shows that the absolute value of Pearson correlation coefficient between these five characteristic parameters and U is above 0.98, and the absolute value of correlation b coefficient of discharge frequency is the largest (r=-0.996 9), followed by slope (r=-0.997 6). According to the U prediction b model fitted by multiple linear regression, R2=0.999 8, RMSE=0.151 5 kV, It shows that the proposed characteristic parameter combination can properly reflect the aging condition of main insulation, which can provide theoretical support and data reference and for on-line monitoring and residual life prediction of generator insulation.

     

/

返回文章
返回